오늘 무엇을 도와드릴까요?

Troubleshooting Site Key Mismatch Error during Upload on Power Advisor Site

Issue
Users may encounter an error message stating, “The provided Site Key does not match the expected Site Key” when attempting to upload on a Power Advisor (PA) site.

Product Line
Power Advisor

Environment
Production

Cause

This error typically occurs when there is a discrepancy between the Site Key in the Customer Relationship Management (CRM) system and the Site Key in the uploaded histfile. The Power Advisor checks both the customer ID and the Site Key during the upload process to prevent data from being mixed across different sites.

Resolution

If this error arises, it’s important to determine the reason for the Site Key alteration. This could be due to a side-by-side upgrade of Power Monitoring Expert (PME), or changes made to the PME server.

If the change is legitimate, please reach out to the Power Advisor system administrator or Level 4 support to update the Site Key in the CRM system. This action should rectify the issue, enabling successful uploads on the Power Advisor site.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
제품군
자세히 알아보기
제품군
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings