Can PowerChute Network Shutdown restart the Computer/Server?
Issue:
How does the operating system restart when AC has been restored?
Product:
PowerChute Network Shutdown
Environment:
All supported operating systems
Cause:
Computer/Server restart automatically required
Solution:
PowerChute is software running on a computer or server. When the system is powered off, PowerChute is no longer available and, therefore, cannot restart the system. This is the same as if the user wants to create a text document. If the system is powered off, the text editor cannot run.
The system BIOS is responsible for automatically starting the system. Many systems available today use an ATX motherboard, which supports a soft switch for turning the system on and off. The implementation of this soft switch includes a BIOS parameter that defines the state the computer enters when the power supply senses input power after being plugged into the wall. This BIOS parameter can have any one of three values :
ALWAYS ON: When power is cycled, the system automatically turns on and boots up.
ALWAYS OFF: When power is cycled on, the system remains off until the user manually presses the On/Off soft switch.
LAST STATE: When power is cycled on, the system will either come on or stay off, depending on whether it was on or off when the power was lost.
Most computer/server manufacturers set this parameter to Last State, and some set it to Always Off. It is improbable to find the Always On parameter setting. In many cases, the computer/server manufacturer allows the user to change this parameter via the system setup menu, which can be accessed before the operating system loads when the computer/server is turned on.
Our recommendation is to set the BIOS to Always On.
Once the BIOS has been configured to allow the OS to restart, the UPS or outlet group must be told to power off. To power off the UPS or outlet group, configure the UPS shutdown within PowerChute Network Shutdown.
If the UPS or outlet group is not commanded off and AC is restored during the shutdown process, the UPS will not cut output, so the BIOS will not restart the system.
NOTE: Some Smart-UPS only allow turning off the UPS; others allow for turning off the UPS or the outlet group, and PowerChute cannot command down a 3-phase UPS.
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.