오늘 무엇을 도와드릴까요?

PowerChute fails to connect with Microsoft smtp-outlook.com and smtp.office365.com to send email notifications.

Issue:

PowerChute fails to connect with Microsoft smtp-outlook.com and smtp.office365.com to send email notifications.

Products:

PowerChute Serial Shutdown v. 1.0, 1.1, 1.2, 1.3

PowerChute Business Edition 9.5, 10.x

Environment:

PowerChute is configured to use a Microsoft SMTP server as the mail server.

Cause:

As of 16 September 2024, Microsoft no longer allows username and password authentication to connect to its SMTP servers. PowerChute used the Microsoft user's username and password to authenticate with Microsoft SMTP servers, so it can no longer connect to send email notifications.

See:

https://techcommunity.microsoft.com/t5/outlook-blog/keeping-our-outlook-personal-email-users-safe-reinforcing-our/ba-p/4164184

Solution:

See Schneider Electric FAQ000274757

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings