브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Plant Scada Secondary server issue (not connecting to OFS running as a Service)

Issue

Is it possible to run OPC Factory Server as a Service and have AVEVA Plant SCADA use it?


Product Line

OPC Factory Server v3.63 (any Service Pack) running under AVEVA Plant SCADA v2023


Resolution

It is not possible to run OPC Factory Server as a Windows Service and for AVEVA Plant SCADA to use it upon launch of Plant SCADA.

AVEVA Plant SCADA was designed to launch OPC Factory Server WSP as a regular Windows Application and not to be run as a Windows Service.


To ensure AVEVA Plant SCADA communicates properly with OPC Factory Server, please deactivate OPC Factory Server running as a Windows Service with these steps:

1. From Windows Services -> Stop OFService

2. Open Windows File Explorer.

3. Navigate to folder: C:\Program Files (x86)\Schneider Electric\OFS\Server\

4. Run ofsnoservice.bat

5. Search for and Run "DCOMcnfg" from the Windows Start Bar.

6. Expand Console Root > Component Services > Computers > DCOM Config

7. Select the Schneider-Aut OPC Factory Server application, then go to Properties,

8. Go to Identity and check "The Interactive user" selector box (to remove the Windows Service User).

9. Confirm and close DCOMcnfg

10. Restart Windows

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings