Power Monitoring Expert Installer Fails at Create Database Folder step due to Access is Denied error

Issue:

PME Installer gives user "access is denied" error at the Create Database Folder step.

Product Line:

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

Power Monitoring Expert Installer

Cause:

PME Folder reverts back to Read-Only even after unselecting the option for the PME Folder properties.

Resolution:

  1. Navigate to the File Explorer
  2. Go to the File path where you have selected the PME folder to be placed during installation.

NOTE: File path should be similar to this example: C:\Program Files (x86) \Schneider Electric

  1. Navigate to the Power Monitoring Expert Folder
  2. Right-click the folder and select Properties
  3. Navigate to the Security Tab
  4. Once in Security select a user from the Groups and User Names option
  5. Select Edit and in the Permissions box select Full Control
  6. Select Apply and OK
  7. Repeat steps 6-9 for all users found in the Groups and User Names section
  8. Once all users have Full Control of the PME folder navigate back to the PME installer
  9. Re-run the failed Created Database Folder step and the installer should finish this step successfully