Installer package error gets returned when upgrading to a newer CE version by installing it on top of an older version.

Windows saves a copy of the installation files for the 'Microsoft C++ Runtime' libraries and 'Control Expert' under the folder named 'C:\Users\Public\Downloaded Installations'.   Depending on the group policy, it might not have had access rights for saving the files to the folder.  If an installer related error gets returned when trying to install a newer version of 'Control Expert' on top of an older version', the issue could be due to the installer software not being able to find the necessary files required to perform the uninstallation of the older version within that folder.

The following steps can be used to resolve the issue:

  • Mount the iso image for the older 'Control Expert' version.
  • Run 'Setup' as an administrator.
  • Select 'Remove' to uninstall 'Control Expert'.
  • Open the 'Programs and Features' in the 'Control Panel'.
  • Uninstall all the DTM libraries that were installed by the older 'Control Expert' version.
  • Reboot.
  • Mount the iso image for the newer 'Control Expert' version.
  • Run 'Setup' as an administrator.
  • Reboot the PC after the installation completes.
  • Open 'Control Expert' to verify that there are no problems.
  • Close 'Control Expert'.
  • Open the 'Security Editor' and verify that it is working.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings