IAP10/20-T Single Point Calibration at Atmospheric Pressure
- X = Atmospheric pressure at time of this calibration
- C = The currently configured M1_LRV prior to this procedure
- Vent transmitter process connection to atmosphere
- Press the NEXT button and display will indicate RERANGE
- Press ENTER and display will indicate M1_URV
- Press NEXT and display will indicate M1_LRV
- Press ENTER and the current M1_LRV value will be displayed with the most significant digit blinking. Before proceeding, write down this value. This is the “C” value
- Press NEXT until the blinking digit is equal to the first digit of the “X” value.
- Press ENTER and the next most significant digit will blink.
- Press NEXT until this digit is equal to the next digit of the “X” value, the press ENTER. Repeat this procedure for the remaining digits.
- After the last digit has been edited, the display will now indicate Place DP.
- Press NEXT until the decimal point is in the desired location.
- Press ENTER and CANCEL will be displayed.
- Press NEXT and SAVE will be displayed.
- Press ENTER and transmitter will return to measurement display.
- Press NEXT 3 times and CALIB will be displayed.
- Press NEXT and CAL AT0 will be displayed.
- Press NEXT and CAL LRV will be displayed.
- Press ENTER and wait for display to indicate LRVdone.
- Repeatedly press the NEXT button until the display indicates SAVE.
- Press ENTER and transmitter will return to the measurement display.
- Press the NEXT button and display will indicate RERANGE
- Press ENTER and display will indicate M1_URV
- Press NEXT and display will indicate M1_LRV
- Press ENTER and the current M1_LRV value will be displayed with the most significant digit blinking.
- Press NEXT until the blinking digit is equal to the first digit of the “C” value.
- Press ENTER and the next most significant digit will blink.
- Press NEXT until this digit is equal to the next digit of the “C” value, the press ENTER. Repeat this procedure for the remaining digits.
- After the last digit has been edited, the display will now indicate Place DP.
- Press NEXT until the decimal point is in the desired location.
- Press ENTER and CANCEL will be displayed.
- Press NEXT and SAVE will be displayed.
- Press ENTER and transmitter will return to measurement display.
- Done