IDP10S-T Re-ranging
Before beginning, the following values must be determined
M1_LRV = Desired differential pressure value for 4mA output
M1_URV = Desired differential pressure value for 20mA output
- Press the NEXT button twice and the word CONFIG will be displayed.
- Press ENTER and POLLADR will be displayed
- Press NEXT 10 times and M1_EGU will be displayed
- Press ENTER and the current engineering unit will be displayed
- Press NEXT until the desired engineering unit is displayed (i.e. FtH2O, inH2O, PSI…)
- When desired engineering unit is displayed, press ENTER and M1EOFF will be displayed
- Press NEXT and M1_URV will be displayed
- Press ENTER and the first digit of the M1_URV will flash. Press NEXT until the desired value is displayed then press ENTER.
- Repeat this process for the remaining digits.
- After pressing ENTER when the last digit has been edited, PlaceDP will be displayed.
- Press the NEXT button until the decimal point is in the desired location.
- Press ENTER and M1_LRV will be displayed
- Press ENTER and the first digit of the M1_LRV will flash. Press NEXT until the desired value is displayed then press ENTER.
- Repeat this procedure for the remaining 4 digits.
- After pressing ENTER when the last digit has been edited, PlaceDP will be displayed.
- Press ENTER and M2 EGU will be displayed
- Repeatedly press the NEXT button until the word SAVE is displayed.
- Press ENTER
Complete