IDP10-T Calibration at 0.00 Differential Pressure
Before beginning, make sure 0.00 D/P is applied to transmitter
- Press NEXT 3 times and CALIB will be displayed.
- Press ENTER and CAL AT0 will be displayed.
- Press ENTER and transmitter will display CALWAIT.
- Wait until transmitter displays AT0done
- Press NEXT 7 times and SAVE will be displayed.
- Press ENTER and transmitter should return to measurement mode indicating 0.00.
- Complete