오늘 무엇을 도와드릴까요?

PME - excessive "Site connected" messages in the system log

Issue
The PME system log is filled with repeating "Site connected" messages, making it difficult to navigate and maintain the system log.

Site connected messages

Product Line
Power Monitoring Expert 7.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment
System Log Events

Cause
Some Modbus TCP devices quickly close idle connections resulting in PME frequently establishing a new connection with the device.

Resolution
Use the VIP to frequently poll a register to serve as a "keep-alive" so the device doesn't close the connection.

1. Review the "Site connected" messages in the system log and take note of each unique site and/or device mentioned, in this example it's occurring with 2 sites "Sub6_XMFRS" and "Sub7_XMFRS":

Identify devices or sites with Site connected messages

2. Open and log into Designer.

3. Go to File > Open and select a VIP, this example will use VIP.DEFAULT:

Open a VIP

4. Click and drag an Arithmetic Module onto the diagram:

Create Arithmetic Module

5. Click on the small blue input circle on the Arithmetic Module then select "NEW Source":

Select NEW Source

6. With the dotted line following your mouse, click on the ION button on the top toolbar:

Click ION button to link

7. Link to a register either on a device or a device under a site that has recurring "Site connected" messages. In this example it's a site so the link will be to a serial device added to the site:

Link to register on device or device under a site with Site connected messages

8. File > Save the VIP, then do shift+left-click on the input circle of the Arithmetic Module to confirm a value is displayed. Note: if linking a serial device under a site and "n/a" is displayed instead of a value, try linking a different serial device that is communicating. If the linked register is not displaying a value, it won't prevent the "Site connected" messages.

Confirm linked register shows value

9. Repeat for remaining devices and/or sites that have recurring "Site connected" messages.

If the messages persist after linking the source, the VIP polling rate will need to be adjusted:

1. Open Management Console > Tools > System > ION Virtual Processor Setup > expand the VIP (used in the previous steps) > Global Parameters.
2. Reduce the Client Polling Period (ms) to 4000, then click Save. Try reducing this further if the "Site connected" messages persist.

Client Polling Period setting

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings