브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Smart UPS Modular Ultra shows RS232 Communication Entry

Issue:

The UPS shows RS232 comm alarm detected 140B-0000 entry every few seconds on the display and power event log.

Example of the event log:

10/01/2024    13:34:26    Device    RS232 comm alarm cleared [140A-00A0].    0x02B8
10/01/2024    13:34:25    Device    RS232 comm alarm detected [140B-00A0].    0x02B9
10/01/2024    13:31:25    Device    RS232 comm alarm cleared [140A-00A0].    0x02B8
10/01/2024    13:31:25    Device    RS232 comm alarm detected [140B-00A0].    0x02B9
10/01/2024    13:28:25    Device    RS232 comm alarm cleared [140A-00A0].    0x02B8
10/01/2024    13:28:25    Device    RS232 comm alarm detected [140B-00A0].    0x02B9
10/01/2024    13:25:25    Device    RS232 comm alarm cleared [140A-00A0].    0x02B8
10/01/2024    13:25:24    Device    RS232 comm alarm detected [140B-00A0].    0x02B9
10/01/2024    13:22:24    Device    RS232 comm alarm cleared [140A-00A0].    0x02B8
10/01/2024    13:22:24    Device    RS232 comm alarm detected [140B-00A0].    0x02B9


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

The firmware has been improved to correctly handle the situation that causes the entry to appear repeatedly in the log.

Please upgrade the UPS to at least firmware 17.0, then clear all alarms if needed.

In order to upgrade the UPS properly, please use the following FAQ - https://www.apc.com/us/en/faqs/FAQ000261838/

If the alarm returns after upgrading the firmware, please contact support.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings