브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
My Smart UPS Modular Ultra has an A671, A681, A691 or A6A1 alarm

Issue:

My Smart UPS Modular Ultra shows one or more of the following alarms.

A671 – Power Module PFC Shutdown: High Positive DC – Hardware Circuit
A681 – Power Module PFC Shutdown: High Negative DC – Hardware Circuit
A691 – Power Module PFC Shutdown: High Positive DC – Firmware
A6A1 – Power Module PFC Shutdown: High Negative DC – Firmware


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers


Resolution:

Usually, the alarm is caused by one of these events below.  The power modules are OK and should not be replaced.

If the alarm is caused by:

  1. An inductive load being applied, reduce the inductive load then clear alarms.
  2. The Service Bypass Unit (SBU) being switched from the "Normal" position to the "Maintenance" position, ensure the UPS is in Bypass by using the "Put UPS into Bypass" command on the display (Control > UPS > Put UPS into Bypass) prior to switching the SBU position.
  3. The output being miswired and another source is backfeeding into the UPS output, ensure the wiring is corrected.

To reset the alarm from the display menu go to Menu > Control > UPS > Clear Alarms.  If you try and clear the alarm too quickly, the Power Module DC buses may not have enough time to discharge which would set the alarm again.  Wait 3 minutes before performing the Clear Alarms action.

If the issue persists, please contact technical support.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings