오늘 무엇을 도와드릴까요?
IDP10-A/IGP10-A Calibrate at Known Tank Level
X = Actual level in tank
- Press the NEXT button twice and the word CONFIG will be displayed.
- Press ENTER and EX ZERO will be displayed
- Press NEXT 7 times and EGU LRV will be displayed
- Press ENTER and flashing cursor will appear at the left side of display along with a number value (Make note of this value)
- Press ENTER and the left most digit will flash
- Press NEXT until this digit matches the value of the most significant digit of the X value then press ENTER. Repeat procedure for the remaining 3 digits until the entire X value has been entered
- Press ENTER and SET DP will be displayed
- Press NEXT until the decimal point is in the correct location
- Press ENTER and EGU URV will be displayed
- Press NEXT twiceand SAVE will be displayed
- Press ENTER and device will be returned to Measurement Display
- Press the NEXT button and CALIB will be displayed
- Press ENTER and display will indicate CAL AT0
- Press next and display will indicate CAL LRV
- Press the ENTER button and display will indicate LRVDONE
- Press NEXT 5 times and SAVE will be displayed
- Press Enter
- Press the NEXT button twice and the word CONFIG will be displayed.
- Press ENTER and EX ZERO will be displayed
- Press NEXT 7 times and EGU LRV will be displayed
- Press ENTER and flashing cursor will appear at the left side of display along with a number value
- Press ENTER and the left most digit will flash
- Press NEXT until this digit becomes 0 then press ENTER. Repeat procedure for the remaining 3 digits.
- Press ENTER and SET DP will be displayed
- Press NEXT until the decimal point is in the correct location
- Press ENTER and EGU URV will be displayed
- Press NEXT twiceand SAVE will be displayed
- Press ENTER and device will be returned to Measurement Display
- Complete
게시 대상: 슈나이더 일렉트릭 Korea