What is the Maximum capacity of the SURT013?

Question:

What is the Maximum capacity of the SURT013 equipment cart?

Product Line:

SURT013

Environment:
Smart-UPS UPS

Solution:

The maximum recommended capacity of the SURT013 is 550Lbs based on its design. While the cart has 4 pieces of 650 lbs rated casters but we do not suggest exceeding the 550 limit. The limit takes the cart's weight and includes a safety buffer to accommodate dynamic load weight when in motion. Installing  equipment that exceeds this weight  may cause damage to equipment or may result to injury.

Unit is made specifically for the  SURT15KRMXLT and SURT20KRMXLT using it with other equipment is not recommended.

SURT15KRMXLT and SURT20KRMXLT UPS units may be stacked to a total height of not more than 18U on its own on the floor without the cart. But when using cart only UPS and First Battery pack should be installed and additional accessories such as additional External packs , Stepdown Transformers should be installed in a separate cart.

Here are the UPS supported and  Battery packs and their weight.

  • SURT15KRMXLT - 546.15 lbs(US) (247.73 kg)
  • SURT20KRMXLT  - 546.15 lbs(US) (247.73 kg)
  • SURT192RMXLBP2 - 400.84 lbs(US) (181.82 kg)

Here are some SURT15KRMXLT and SURT20KRMXLT configuration bundles that when installed Needs to be split in multiple carts because it exceeds weight capacity.

  • SURT15KRMXLT-TF5 - 641.35 lbs(US) (290.91 kg)
  • SURT20KRMXLT-TF5 - 641.35 lbs(US) (290.91 kg)

Image shows SURT013 Equipment Cart with no load

If you have any clarifications or concerns, please do contact us at 1-800-800-4272 or chat with our Technical Support Agents.

*Attached on this article is the user guide that shows top and bottom Image of cart and shows in detail how the UPS is mounted and installed on equipment cart.

슈나이더 일렉트릭 Korea

첨부 파일
SURT013 User Guide.pdf [90.81 KB]
자세히 알아보기
제품군
제품군
자세히 알아보기
제품군
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings