HDPM6000 Energy Log will not roll over
Issue:
Customer is having an issue with the Energy Values from a HDPM6000 device will log into Power Monitoring Expert even though the Energy logs are set to roll over on the meter webpage.
Product Line:
HDPM6000
Environment:
HDPM6000 Firmware V6.2.11 Energy Logs
Power Monitoring Expert
Cause:
Even though the Energy logs are configured to roll over on the meter's webpage, the firmware does not recognize this setting, causing the meter to stop logging energy values into Power Monitoring Expert.
Resolution:
As of now the workaround is to manually reset energy values either through Modbus writes or web page of meter. Next firmware release after V6.2.11 will address this behavior and roll over the energy as expected.
For more information on how to perform a Modbus write using Modbus Tester please refer to the article: FA180037
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.