Why do my string displays show squares when the string is coming from my PLC?
Issue:
Why do my string displays show squares when the string is coming from my PLC?
Product Line:
Vijeo Designer, HMIs
Environment:
Vijeo Designer
Resolution:
Why do my string displays show squares when the string is coming from my PLC?
Please click into your IO Manager Driver node and check what the "String Encoding" is set as:
The default is ASCII and it should be set to ASCII for strings
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.