오늘 무엇을 도와드릴까요?

ION Meters IEC61850 Data Object (DO) and Data Attribute (DA) level definition requirements

Issue
ION Meters reject CID files with 'Invalid CID File' Error and log "'daName' Attribute must be specified in data set member" in /IEC61850 folder.

_____________________________________________________________
Product Line
Product Models: ION9000, PM8000, ION7400, ION8650, ION7650
_____________________________________________________________
Environment
SCL File Editor CET850
_____________________________________________________________
Solution

The ION Meters do not support a CID file based on Data Object Level. The CID parser in ION meters will be looking for the DaName attribute and will reject the file if the parser cannot find this.

To ensure compatibility and proper DataSet configuration for ION meters, define DataSets using both DO Name(Data Object Level) and DA Name(Data Attribute Level).

As shown in the CET850 tool (see image), each entry in the DataSet must include:

- DO Name (e.g., TotW, TotVA, TotVar)
- DA Name (e.g., mag, phsAB.cVal, phsA.cVal)

Data Object and Data Attribute levels

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings