How to retrieve log files from a controller in EAE BT

1.Open EAE Buildtime and load the EAE Solution currently running on your controller.

2. Navigate to the Deploy & Diagnostics tab.

3. Log in to the device.

4. Expand the Action tab for your controller, then go to Log File > Fetch log files to retrieve the files.

M580d fetch log

5. Wait for the message: "Fetching of log file successfully finished."

action progress

6. Close the Device Log Viewer pop-up window.

7. Locate the cyclic.log and device.log files in the following path (also see note c. below)
Documents\Schneider Electric\EcoStruxureAutomationExpertProjects\<project_folder(s)>\IEC61499\Log

8. Send both files to Technical Support.

NOTES:

a. This Knowledge Article was made based on EAE version 24.1.

b. For SoftdPAC HA configurations, log files should be fetched from the parent controller menu to ensure that the cyclic and device logs for both the left and right iPCs are retrieved. Make sure to send all four files to Technical Support.

HA fetch log

c.  The path to retrieve the log files from your controller can also be retrieved from the Device Log Viewer pop-up window, by:

  • Clicking on File > Load Log
  • In the Open Log file window, right click on the folder address and click on Copy address as text

retrieve path

  • Open a File Explorer window, edit address and paste the one retrieved from the Log window. Press ENTER.

file explorer

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
제품군
자세히 알아보기
제품군
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings