오늘 무엇을 도와드릴까요?

Can the BMXNOR0200H module's Ethernet communication be reset using IO_DDT (ETH_RESET)?

1. Issue
Some customers have reported that the online help in Control Expert suggests BMXNOR0200H supports Ethernet communication reset via IO_DDT (ETH_RESET). However, this functionality is not supported. The only available method to reset the Ethernet communication is through the module’s web interface.

2. Product Line

  • Module: BMXNOR0200H

  • Software: Control Expert

3. Environment

  • Operating System: Windows 10 / Windows 11

  • Software: Control Expert

  • Browser: Any standard browser used to access the module’s web interface

4. Resolution
After consultation with R&D, it has been confirmed that BMXNOR0200H does not support Ethernet reset via IO_DDT. The only supported method is through the web interface of the module.

Note:
No updates to the user manual are planned. It is recommended to use the BMENOR2200H (Advanced RTU module) instead, which supports Ethernet reset via Device DDT.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings