오늘 무엇을 도와드릴까요?
What is the minimum clearance between phases and ground for the secondary side connections for Trihal Transformers?
Issue:
Minimum clearance between phases and ground for the secondary side connections for Trihal Transformers
Product Line:
Trihal Medium Voltage Transformer
Resolution:
For low voltage connections (< 1100 V), the standardized distances between phases are defined by standards IEC 1439 and IEC 60664-1.
For a nominal voltage of 1000 V, with an overvoltage category III (impulse voltage of 8000 V) and a pollution degree 3 (industrial environment), the minimum air gap between two conductors is 8 mm.
Distance between phases:
Minimum 8 mm
Distance between phase and ground:
Minimum 10 mm with an insulating screen
Minimum 21 mm in air
Please see attached file for reference
게시 대상: 슈나이더 일렉트릭 Korea