Implementing a Heartbeat Signal to Trigger Syslog Messages on SAGE RTU
Issue:
Customer needs a method to generate a periodic syslog message to meet NERC CIP compliance by proving syslog functionality for monitoring systems like SPLUNK.
Product:
SAGE RTU (all models supporting syslog and command logging)
Environment:
- Centralized syslog monitoring system (e.g., SPLUNK)
- Requirement for periodic heartbeat messages to validate syslog operation
- RTU configured with syslog enabled
Cause:
There is no built-in “heartbeat” feature in the SAGE RTU to automatically send syslog messages. However, syslog messages can be triggered by logging events such as command executions.
Resolution:
- Recommended Approach:
- Configure an hourly toggling of a Digital Output (DO) point using a Data Transfer point created specifically for this purpose.
- Each toggle will generate an entry in the Command Log, which in turn sends a syslog message to the monitoring system.
- This achieves the heartbeat function without requiring custom code.
- Steps:
- Please refer to the PDF document attached to this article, titled:
“Create an hourly heartbeat DO command that will trigger Command Log to deliver the event notification to Syslog server.”
- Please refer to the PDF document attached to this article, titled:
This method provides an “elegant” solution using existing RTU functionality and satisfies compliance requirements.