How to Configure Secure Services (HTTPS, SSH, and RADIUS) on SAGE RTU

Title:

How to Configure Secure Services (HTTPS, SSH, and RADIUS) on SAGE RTU

Issue:

Need to enable secure communication and centralized authentication on SAGE RTU for compliance and cybersecurity.

Product:

SAGE Remote Terminal Unit (RTU) All models

Environment:

  • Firmware version C3414-500-S02YZ or later
  • Config@WEB GUI accessible via HTTPS
  • User Manager and Configuration Converter tools installed on PC (.NET Framework 3.5+)

Cause:

Default configuration may allow insecure protocols (HTTP, Telnet, FTP). Secure services must be enabled to meet security standards and prevent unauthorized access.

Resolution:

1.- Enable Secure Services via GUI:

  • Navigate to CPU Configuration → Services Setup.
  • Select the following options for maximum security:
      • HTTPS (Port 443) for encrypted web access
      • SSH Server (Port 22) for secure remote shell
      • SFTP for secure file transfer
      • Enable Remote Shell for VxWorks shell access
      • IPsec for VPN traffic encryption
      • Enable RADIUS Authentication for centralized user management

2.- Configure RADIUS Authentication:

  • Enable RADIUS client in CPU Configuration.
    • Click Configure Servers and enter:
      • IP Address of RADIUS server
      • UDP Port (default 1812)
      • Retries and Timeout values
      • Shared Secret (must match on RTU and RADIUS server)
  • Up to 5 RADIUS servers can be configured.

3.- Generate and Install Keys:

  • SSH: Generate DSA/RSA keys for RTU and users; include in user package via User Manager.
  • HTTPS: Replace default SSL key and certificate using Configuration Converter; generate custom files externally.

4.-Apply Changes:

  • Upload updated configuration via GUI Up/Download tab.
  • Perform RTU reset for changes to take effect.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings