Modbus Slave Communication protocol on PowerLogic P5 Protection Relays
Issue:
How to configure and use Modbus Slave protocol for PowerLogic P5 relays, including supported modes, function codes, and integration requirements.
Product:
PowerLogic P5 Protection Relay
Environment:
SCADA systems using Modbus RTU (RS-485/fiber) or Modbus TCP/IP (Ethernet)
Industrial networks with multi-protocol support
Configuration tools: eSetup Easergy Pro, Web HMI, front panel
Cause:
Modbus is widely used for simple and reliable data exchange in automation systems. Incorrect configuration of addressing, scaling, or function codes can lead to communication errors, data mismatch, or control failures.
Resolution:
- Protocol Support:
- Modbus RTU: RS-485/fiber, 1200–115200 bps, 2/4-wire
- Modbus TCP/IP: Ethernet, port 502, up to 3 IP addresses/subnets
- Supports up to 8 clients and 4 slave instances
- Configuration:
- Set protocol via COMMUNICATION menu or eSetup Easergy Pro/Web HMI
- Parameters: Slave address (1–247), baud rate, parity, scaling, IP filtering
- Function Codes:
- 03 (Read Holding), 04 (Read Input), 06 (Write Single), 16 (Write Multiple), 23 (Read/Write Multiple), 07 (Read Exception Status), 08 (Diagnostics), 11 (Comm Event Counter), 43/14 (Device ID), 20 (Disturbance file)
- Data Model:
- Extensive register mapping for protection, measurement, control, alarms, events, and settings
- Data types: Bool, Enum, Int16/32/64, UInt16/32/64, float32, string
- Scaling examples: 1.00 s = 100, 50.00 Hz = 5000
- Features:
- Real-time measurements, event logs, disturbance records
- Control commands: Open/Close, Select/Execute, latch release, setting group change
- Clock sync via registers (2504–2507)
- Security:
- No encryption; use VLANs, firewalls, IP whitelisting (CIDR, up to 8 entries)
- Port/protocol enable/disable; sFTP for secure file transfer
- Integration:
- Compatible with SCADA, EvoPact HVX, external AI/DI/DO
- Supports redundancy (PRP, HSR, RSTP)
게시 대상: 슈나이더 일렉트릭 Korea
도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.