브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Does the ACRC301S is compatible with BACnet?

Issue:

¿Does the ACRC301S is compatible with BACnet?

Product Line:

Inrow Cooling units Gen 2 (300 mm)

Environment:

ACRC301S and ACRC301H

Cause:

The customers have doubts and confusion about the compatibility of the ACRC301S with BACnet configuration, due that the operation manual doesn’t include the corresponding paths.

The ACRC301S is compatible with BACnet, depending on the firmware version of the unit.

The newest models already came with a firmware version of v6.0.0 and higher and are supported by BACnet.

The corresponding path to configure this monitoring system is the following: Main > Configuration > Network > BACnet, this path is found at the Online Guide as well as the BACnet Application Map.

For old units, the application firmware should be v2.4.2.1+ for InRow CW ACRC301S and ACRC301H cooling units supports BACnet/IP only.

Resolution:

These models (ACRC301S and ACRC301H) are supported by BACnet, you just need to confirm the firmware version at the unit, use as reference the Online Guide and BACnet Application Map.

슈나이더 일렉트릭 Korea

첨부 파일
990-2022726_Online Guide_ACRC301S-ACRC301H_Sign Off (1).pdf [818.67 KB]
TME27091-ACRC3xx BACnet Application Map (1).pdf [121.17 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings