오늘 무엇을 도와드릴까요?

How to export a variable value from a PLC ?

Issue:
Ho to export a variable value from a PLC program to be imported in another program

Product Line:

EcoStruxure Control Expert

Environment:

  • EcoStruxure Control Expert
  • M340 / M580 / Premium / Quantum PLCs

Resolution:

Exporting Variable Values from PLC

To access variable values already defined in the PLC program, you can use the Export DTX File feature in EcoStruxure Control Expert. This file can later be re-imported into the same project.

Note: This operation can only be performed when connected to the CPU.

Steps to Export Data:

  1. In EcoStruxure Control Expert, go to the top menu, click PLC, and select Save Data from PLC.
  2. A new window will open.

screenshot1

Depending on the variable type, select the appropriate options and specify the destination file.

Restoring Data from a Previously Exported .DTX File

Steps to Restore Data:

  1. In the top menu, click PLC and select Restore Data from File to PLC.
  2. If the controller is in RUN mode, a message will appear allowing you to:
    • Proceed with the transfer while the controller continues operating (OK), or
    • Cancel the transfer.
  3. A dialog box opens. Select the file to import and click Open.
  4. A confirmation message will ask if you want to proceed with the transfer.

Fore more details , please refer to the attached PDF file.

슈나이더 일렉트릭 Korea

첨부 파일
Save-restore data.pdf [313.93 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings