오늘 무엇을 도와드릴까요?

UL Certificate of Conformity for Harmony HMISTU and HMISCU families of Human Machine Interfaces

Issue

Where do I find the UL Certificate of Conformity for Harmony HMIGTO targets and which UL enclosure types are they rated for?

Product Line

Harmony HMISTU

Harmony HMISCU

Environment

Physical characteristics

Resolution

Attached are the pdf UL Certificate files of Conformity for Harmony HMISTU and HMISCU targets.

"E210412-Vol3-Sec26-UL CoC.pdf"

"E220851-Vol3-Sec45-UL CoC.pdf"

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

첨부 파일
E210412-Vol3-Sec26-UL CoC.pdf [543.71 KB]
E220851-Vol3-Sec45-UL CoC.pdf [543.5 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings