오늘 무엇을 도와드릴까요?

Is EcoStruxure Machine SCADA Expert v2023 compatible with the HMIG5U21?

Issue:

Can Machine SCADA Expert v2023 run correctly in the Harmony GTU HMI open box HMIG5U21?

Product:

  1. EcoStruxure Machine SCADA Expert v2023
  2. HMIG5U21

Environment:

  1. HMI Configuration Software in Windows
  2. Harmony GTU HMI open box with Windows 10 IoT

Resolution:

Short answer: In theory it is compatible but it is not recommended.

EcoStruxure Machine SCADA Expert v2023 have the following requirements:

From: EcoStruxure™ Machine SCADA Expert , Help Manual - 07/2024 - P.38

1

The HMIG5U21 barely meets these requirements:

From: HMIG5U21 product data sheet

2

Note: Keep on mind that the actual available memory might be less than 4 GB, especially if the OS and other tasks are running.

From: Harmony GTU, User Manual - 01/2022 - P.12

3

The HMIG5U21 is theoretically compatible with EcoStruxure Machine SCADA Expert v2023; however, it is not recommended for Machine SCADA Expert applications. Machine SCADA Expert projects are typically complex and may require even more system resources.

Related resources:

Title: EcoStruxure™ Machine SCADA Expert, Help Manual

URL: https://download.schneider-electric.com/files?p_Doc_Ref=EIO0000002448&p_enDocType=User+guide&access=Public

Title => "Harmony GTU, User Manual"

URL => https://download.schneider-electric.com/files?p_Doc_Ref=EIO0000001735&p_enDocType=User+guide&access=Public

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
제품군
자세히 알아보기
제품군
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings