오늘 무엇을 도와드릴까요?

How to accomplish integration between Machine SCADA Expert and a live video feed from a camera?

Issue:

This FAQ explains how integration between Machine SCADA Expert and a live video feed from a camera is possible.

Product:

EcoStruxure Machine SCADA Expert v2020, v2023

Environment:

HMI Configuration Software in Windows

Resolution:

The multimedia function in EcoStruxure Machine SCADA Expert only supports audio; there is no built-in feature for direct camera integration.

These applications depend entirely on the camera’s capabilities.

If the camera supports a web server, you can use the Webpage widget (recommended instead of the obsolete ActiveX webpage) to display the camera’s web interface, for more information regarding this widget check FAQ000268760.

If the camera supports an open streaming protocol, integration is possible through a custom widget, using a syntax such as: protocol://mycamera:streaming_port

Some cameras provide ActiveX controls or VLC-based streaming options.

Therefore, you must verify your camera’s capabilities to determine the available integration method.

There is no generic solution for these applications, as each camera has different features.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings