오늘 무엇을 도와드릴까요?

MCS (Modicon Communication Server) | OCMC Displays "Could not read Configuration" Error When Accessing Settings

Description
When opening the Settings page in the Modicon Communication Server, the following message may appear:

“Could not read Configuration. Please restart the 'ModiconCommunicationServer Configuration Server' and 'Modicon Communication Server UI Service' from Services.”

img1

Product Line

  • MCS

  • Modicon Communication Server
  • EcoStruxure Process Expert for Aveva System Platform
  • OCMC

Environment

  • Windows Server

Cause
This issue can occur when Internet Explorer Enhanced Security Configuration (IE ESC) prevents the console from loading the configuration interface properly.

Resolution

  1. Open Server Manager on the affected machine.

  2. Navigate to Local Server and locate IE Enhanced Security Configuration.

  3. Set IE ESC to Off for administrators and users.

  4. Restart the computer.

After the restart, the OCMC Settings page should open normally.

img2

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings