오늘 무엇을 도와드릴까요?
How to Install All Reports
Issue:
When running the installer after an upgrade you may run into an issue where the reports are not showing up as an option for you to select.
Product Line:
Power Monitoring Expert (PME) 2020
Power Monitoring Expert (PME) 2021
Power Monitoring Expert (PME) 2022
Power Monitoring Expert (PME) 2023
Power Monitoring Expert (PME) 2024
Environment:
Power Monitoring Expert (PME)
Command Prompt
Resolution:
Note: Please first verify that the Report Packs are present and in the correct path. They will be saved in the Power Monitoring Expert root folder found in ...\Power Monitoring Expert\Web\Report Packs (like C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Web\Report Packs)
Note (2): Only the reports that are already present within the folder will install even though all reports are listed.
-
Run Command Prompt as Administrator.
-
Run
cd C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\bin(change the path if required). -
Run
ReportPackUtil.exe -root "C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Web" -install "Default Reports,Billing Reports,Energy Reports,Xpert Trending Analysis Reports,Usage Reports,Branch Circuit Energy Reports,Branch Circuit Power Reports,BreakerAgingReports,EPSS_CoreReports,EPSS_TestReport,Energy Management Reports,Generator Power Reports,InsulationMonitoring_Reports,Power Loss Reports,PowerQualityAdvisor,PUE Reports,ModelingReports,Regression Reports,Pue Reports,Regression Reports,Pue Reports,ModelingReports Dashboard Reports,KPIReports,StandardPowerQuality Reports,UPS Power Reports,EPSS_UPS_AutoTestReport,Capacity Management Reports" -
Run
Reporting.ReportUpgrade.exe Default_ReportUpgradeInstructions.xml -
Run
Reporting.ReportUpgrade batch
게시 대상: 슈나이더 일렉트릭 Korea