오늘 무엇을 도와드릴까요?

PME 2024 R2 - Installer steps "Update File Permissions" and "Registering Windows Services" are unsuccessful

Issue

During a fresh install, the "Update File Permissions" and "Registering Windows services" steps are unsuccessful. None of the PME Windows services are installed. The install log shows errors:

  • Update File Permissions fail: MethodHandler encountered a problem while calling 'Installer.InstallTools.WinUtilities.AssignReadWriteFolderControl': InstallTools.Utility.VariableInterpolationException: Variable lookup does not contain a definition for the variable 'globalNetworkServiceLocalizedNameNoDomain' --- > System.Collections.Generic.KeyNotFoundException: The key 'globalNetworkServiceLocalizedNameNoDomain' was not found in VariableLookup.
    • <AssignReadWriteFolderControl>
      Library="WinUtilities"
      Class="Installer.InstallTools.WinUtilities"
      UIMessageOnFail="Could not set user permissions on Config folder">
      <userName>@globalNetworkServiceLocalizedNameNoDomain/@</userName>
      <folderName>@globalProgramFileFolder/@\Applications\Dashboards\App_Data</folderName>
      </AssignReadWriteFolderControl>
  • Variable lookup does not contain a definition for the variable 'globalLocalSystemLocalizedName' ---&gt; System.Collections.Generic.KeyNotFoundException: The key 'globalLocalSystemLocalizedName' was not found in VariableLookup

Registering Windows Services error

Product Line

Power Monitoring Expert 2024

Environment

Install/Upgrade

Cause

The Windows account used to run the installer is the built-in Administrator account. For cybersecurity reasons, this account has restrictions on it and shouldn't be used to perform software installations. It's primarily intended for initial system provisioning or disaster recovery.

Resolution

Run the installer with a local Windows user:

  1. Open the Windows Start Menu, search for and open "Computer Management"
  2. Open Local Users and Groups > Users
  3. Right-click > New User
  4. Enter a User name and a password that meets the minimum requirements per the IT policy, then uncheck "User must change password at next logon".
  5. Click Create then close the window.
  6. Add this user to the local Administrators group.
  7. Add this user to SQL Server with sysadmin permission.
  8. Shift + right-click the MainSetup.exe of the PME installer > Run as different user > enter the credentials for the newly created user

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings