How to fix "Failed to open the Symbol file" when trying to link a .xvm file in Vijeo Designer?

Issue

When trying to use the xvm file to link the variables from Control Expert into Vijeo Designer, the following message shows:

"Failed to open the Symbol file. The format of the specified file may be invalid or additional software may need to be installed in order to open the file."

Product Line

Vijeo Designer

Cause

The SRCSDK dll is not registered properly on the PC

Resolution

1/ Go to the following folder:

"C:\Program Files (x86)\Common Files\Schneider Electric Shared\SRCSDK".

It should look something like this

SRCSDK folder

2/ Run Command Prompt as administrator.

3/ Enter:

"cd C:\Program Files (x86)\Common Files\Schneider Electric Shared\SRCSDK"

Then enter:

"regsvr32.exe SRCSDK.dll"

Picture for reference:

Command prompt with commands and confirmation

4/ After getting the confirmation window shown above, restart windows OS and link the .XVM file to VJD again.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings