Explaining the Modbus Scanner - Diagnostic Objects and Exception Responses

The Modbus Scanner in Remote Connect is meant to simplify Modbus polling so that it does not have to be managed via logic. If a user finds the scanners too restrictive for their desired polling scheme, the MB_SERIAL_MASTER and MB_IP_MASTER function blocks can be used in logic and triggered as needed.

The Modbus Scanner in RemoteConnect automatically creates diagnostic objects (like Message Count and Communication Status) for each Modbus Server Device, but does NOT create objects for each individual scanner. Please note: in order to not be overwhelmed by too many objects, objects are created for only the most commonly used diagnostic parameters . A user is welcome to create objects and associate them with additional diagnostic elements.

Modbus Scanner Server Device default Parameters

Situations may arise where the Modbus Scanner is communicating but data is not being read or written. The Remote device could be sending an Exception Response back to the SCADAPack. An Exception Response from a remote device indicates that it understood the message (good comms) but that it is unable to perform the request (invalid function code, invalid Modbus register address, etc... )   The diagnostic objects can be used to help identify the issue and the appropriate resolution.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings