Machine Expert, how can we prevent the controller password to expire?

Issue:

I set up a few of these M241s in the field. Of course, during initial setup I set a login and password.

I noticed that this seems to have expired, requiring me to set a new password. Is there any way to make the password permanent?

Product Line:

Machine Expert version 2.3 and 2.5.

Resolution:

To prevent the expiry of the password to access the controller:

In Machine Expert:

1- From the Device tree, double click on the controller to open the properties and go to the Communication Settings tab.

Communication Settings Tab

2- Click on the Security Settings button to open the following Device Security Settings window.

Device Security Settings

3- Open the CmpUserMgr node.

In it, you will have access to disable the Password Expiration parameter.

User Management parameters

For more details on these parameters consult the online help:

https://product-help.se.com/ESME/2.3/VLP_Software/VLP_Programming/en-US/SoMProg?t=SoMProg/D-SE-0083385.html&theme=ESME

In Machine Expert v2.3 and 2.5, this parameter is enabled by default.

Since version 2.6, it is now disabled by default.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기

제품군

자세히 알아보기

제품군

도움이 필요하신가요?

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.