Recommended Firmware Update for PM5500 Series Meters

As part of our ongoing commitment to product quality and reliability, Schneider Electric continuously monitors field performance, reviews customer feedback, and takes appropriate actions to ensure the highest standards of product performance.

During a recent quality assessment, we identified an observation related to firmware version 4.5.0, where there is a remote possibility of communication instability in a limited number of PM5500 series meter installations. While the occurrence appears to be isolated, we are proactively informing customers and recommending precautionary measures to help ensure continued reliable operation and maintain optimal system performance.


Recommended Action
As a preventive measure, we recommend updating affected meters to the firmware versions listed below until the next firmware release becomes available. For new installations, we also recommend applying the listed firmware version prior to commissioning. This recommendation is intended to maintain optimal communication performance and minimize the possibility of service interruptions.


Affected Models and Recommended Firmware Versions

ModelCurrent Firmware Recommended Firmware
PM55604.5.04.4.7
PM55634.5.04.4.7
PM55804.5.04.4.7
PM56504.14.04.13.0
PM556112.5.012.4.1

Our engineering teams are actively investigating the observation and working on a permanent resolution. We will update the article once the new solution is available.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings