오늘 무엇을 도와드릴까요?

AGA-8 2017 Detail vs GERG Gas Composition Tables in Realflo

When attempting to modify a gas component value in the AGA-8 gas composition table in Realflo, the software displays the following error message: "Enter a number between 0 and 12."

As a result, the new proposed value cannot be entered or saved.

Example:

  • Current Propane (C3H8) value: 20.68%
  • User attempts to enter a value greater than the allowed range.
  • Realflo displays the error and rejects the change.

Real1

This behavior is typically caused by a component value exceeding the permitted range for that gas constituent.
In the example shown in the AGA8-8 Gas Component Ranges Table, Realflo (AGA-8 (1994)) only allows values between 0 and 12% for the selected field.
AGA8-8 Gas Component Ranges Table:
Real2
The Compressibility Calculation selection must change from AGA-8 (1994) to AGA-8 (2017) GERG to increase the allowable range while still making sure that the Total Components add to 100%.
Real3

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터