오늘 무엇을 도와드릴까요?

RemoteConnect x70 Logic Editor Does Not Retain Custom Logic Editor Color Settings

Issue

When using the x70 Logic Editor in RemoteConnect with a SCADAPack 474i, customized logic editor color settings may not behave as expected.

The following behavior may be observed after changing the color settings:

  • The page background changes to black, making the logic difficult to read.
  • Customized color settings are not retained.
  • The settings revert to their default values.

Environment

  • Product: SCADAPack 474i
  • Software: RemoteConnect
  • Component: x70 Logic Editor / Control Expert Logic Editor
  • Languages: FBD, ST, and LD
  • Configuration: Logic editor color settings in standard RGB format

Workaround

As a workaround, the required settings can be configured by directly modifying the applicable .ini file.

The following configuration files can be used depending on the programming language:

  • FBD (Function Block Diagram): FBDcolors.ini
  • ST (Structured Text): STColors.ini
  • LD (Ladder Diagram): LDColors.ini

Procedure

  • Close the Control Expert / x70 Logic Editor.

Location

  • Locate the applicable .ini file for the programming language being configured:
    • FBDcolors.ini for FBD
    • STColors.ini for ST
    • LDColors.ini for LD

Below is the image showing customization between Boolean TRUE and FALSE states for users

colors

  • Before making any changes, create a backup copy of the original .ini file and store it in a safe location. This allows the original configuration to be restored if required.
  • Open the applicable .ini file using a text editor such as Notepad++.
  • Modify the required color settings in the file.
  • Other configurable fields available within the applicable .ini file can also be modified using the same method, where required.
  • Save the modified .ini file.
  • Launch the Control Expert / x70 Logic Editor again.
  • Verify that the modified settings are applied as expected.

Important: Always take a backup of the original .ini file before modifying it. If the modified settings result in unexpected behavior, or if the original configuration is required again, restore the backed-up file.

Additional Information

The same approach can be extended to the different x70 Logic Editor programming languages by modifying their corresponding configuration files:

  • For FBD, modify FBDcolors.ini.
  • For Structured Text (ST), modify STColors.ini.
  • For Ladder Diagram (LD), modify LDColors.ini.

The settings available for modification depend on the fields present in each .ini file. Only existing configuration fields should be modified.

Resolution

Directly modifying the appropriate .ini file provides a workaround when color settings changed through the graphical interface are not retained or displayed correctly.

This method can also be used to modify other applicable configuration fields contained within the respective .ini files.

If necessary, the original settings can be restored using the backup copy created before making the changes.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터