Video: How can you reset the run time and power on time counters on the ATV630 and ATV930 process drive?

Article available in these languages: Финский

Issue:
How can you reset the run time and power on time counters on the process drives?

Product Line:
ATV630 ATV930 Process drive

Cause:
Needs to reset the run time and drives power on time counters.

Resolution:



From Main menu,
then Complete settings and press enter,
then go to Maintenance and press enter,
then Time Counter reset and press enter.

Choose:
Run time rest
Power on time rest
Reset Fan counter
Clear NSM

Logic address: 3244

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings