Issue:
Customer cannot get their Process Drive to run. Top line of the display reads status PWS.
Product line:
Altivar Process, ATV630, ATV930
Environment:
All
Cause:
SoMove connection
Resolution:
PWS indicates the drive Start/Stop is controlled by the SoMove software. Commands to run from the external terminals or the keypad will not be taken into account. The drive will still follow external analog signal.
Customer cannot get their Process Drive to run. Top line of the display reads status PWS.
Product line:
Altivar Process, ATV630, ATV930
Environment:
All
Cause:
SoMove connection
Resolution:
PWS indicates the drive Start/Stop is controlled by the SoMove software. Commands to run from the external terminals or the keypad will not be taken into account. The drive will still follow external analog signal.
Опубликовано для:Schneider Electric Казахстан



