Video: How do you set up a command switch via logic input on the ATV630 and ATV930 drives?
Issue:
How do you set up a command switch via logic input on the ATV630 and ATV930 drives?
Product Line:
Altivar Process ATV630 and ATV930 drives
Environment:
All
Cause:
Need to use a logic input to switch between two command functions like HMI start stop and terminal start stop.
Resolution:
Programming
Press the Home button.
Scroll down to menu 5 complete settings enter.
Scroll down to menu 5.5 command and references enter
Scroll down and choose command switching and assign it to DI3 enter
Scroll down and choose CMD channel 1 for your first command and CMD 2 for your second command.
How do you set up a command switch via logic input on the ATV630 and ATV930 drives?
Product Line:
Altivar Process ATV630 and ATV930 drives
Environment:
All
Cause:
Need to use a logic input to switch between two command functions like HMI start stop and terminal start stop.
Resolution:
Programming
Press the Home button.
Scroll down to menu 5 complete settings enter.
Scroll down to menu 5.5 command and references enter
Scroll down and choose command switching and assign it to DI3 enter
Scroll down and choose CMD channel 1 for your first command and CMD 2 for your second command.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.