Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
Why doesn't the BMXAMO0410 report a channel fault in an open circuit condition?

Issue:

Why doesn't the BMXAMO0410 report a channel fault in an open circuit condition?

Product Line:

BMXAMO0410

Resolution:

One common reason is that the "Wiring CTRL" option box for the specific channel has not been selected. If the option is not selected the Channel Fault bit will not sense for open loop. (open ckt).
The ability to detect a broken wire (open circuit) condition is limited to current outputs. The selection is made in the BMXAMO410 configuration screen.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)



Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings