Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
Where to find the "Runtime Address" when doing tag integration with Machine SCADA Expert and Machine Expert?

1.Issue:
Where to find the "Runtime Address" when doing tag integration with Machine SCADA Expert and Machine Expert?

2. Product Line:
EcoStruxure Machine SCADA Expert, Harmony P6 ,Harmony iPC ,Box iPC ,Harmony GTU Open Box ,EcoStruxure Machine Expert ,M241 ,M262 ,M251

3. Resolution:
Instead of declaring each variable individually in a driver sheet in Machine SCADA Expert,  the Tag Integration tool can be used to attach all the variables from a Machine Expert project to a Machine SCADA Expert project. When configuring the tool, the Runtime Address will be required, in this field the Nodename declared in the My Controller window in Machine Expert can be used, or the Node Address can also be used.

Runtime Address when doing tag integration in EMSE and ME

The Node Address can be found by hovering the mouse over the PLC displayed in the My Controller window, it will be located next to [Address].

Node Address

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings