What operation mode is recommended for LXM32-EtherCAT, running on TwinCAT-NC

Goals and Symptoms

What operation mode is recommended for LXM32-EtherCAT, running on TwinCAT-NC

Causes and Fixes

In Operation mode CSP (Cyclic Synchronous Position), the position values created by the NC-profile generator will be transmitted to LXM32. Inside of LXM32, a fine-interpolator "moves" the axis from one position step value to the next. This fineinterpolator works with 250µs.

In Operation mode CSV (Cyclic Synchronous Velocity), the position loop is closed in the TwinCAT-NC. In this case, the controller sends velocity values to the drive. In CSV, there is no fine-interpolator active in the drive.

Result:
In CSP the position controller loop performance is higher than in CSV, because it's closed inside of the drive. Because of this, we recommend to use CSP.

Schneider Electric Malaysia

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings