Error when adding an EDS file to EcoStruxure Control Expert library
Product Line:
EcoStruxure Control Expert
Resolution:
When adding an EDS file to the library, the error message below is generated. There could be several reasons for this.
1. Control Expert need to run with administrator rights by right clicking on the Control Expert classic icon and select "run as administrator"
2. The following folder is set to read only C:\ProgramData\Schneider Electric\Unity Pro Generic EtherNetIP DTM\Device Library. Right click on the folder and select properties. Under the General tab, uncheck the read only attribute and select Apply
Released for: Schneider Electric Malaysia
Error when adding an EDS file to EcoStruxure Control Expert library
Product Line:
EcoStruxure Control Expert
Resolution:
When adding an EDS file to the library, the error message below is generated. There could be several reasons for this.
1. Control Expert need to run with administrator rights by right clicking on the Control Expert classic icon and select "run as administrator"
2. The following folder is set to read only C:\ProgramData\Schneider Electric\Unity Pro Generic EtherNetIP DTM\Device Library. Right click on the folder and select properties. Under the General tab, uncheck the read only attribute and select Apply
Released for: Schneider Electric Malaysia




Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.