How can we help you today?

BootP doesn't not work after updating to Exec Firmware version 4.1

Issue
BootP doesn not work after updating to Exec Firmware version 4.1

Product Line
140NOE77101 version 4.1 and greater.

Environment
Windows 7

Resolution
The reason why this happens is because a verification step was added in 'Exec Frimware version 4.1'
This step caused the 140NOE77101 to perform a check for the subnet mask other than 000.000.000.000.
To resolve the problem, specify a subnet mask in the bootp configuration.

Schneider Electric Netherlands

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.