How can Altivar ATV312 be set to speedreference by jogdial and commands by terminalblock ?
Goto menu CtL- [ COMMAND ] and set parameter LAC [ ACCESS LEVEL ] to L2 or L3.
Then, also in menu CtL-, set parameter Fr1 to AIUI and parameter CHCF to SEP.
Go back to ready status ( rdY on the display ), push the jogdial to display rEF- and push again.
AIUI appears on the display, by pushing the jogdial again, it will be activated to set the speed by turning.
Then, also in menu CtL-, set parameter Fr1 to AIUI and parameter CHCF to SEP.
Go back to ready status ( rdY on the display ), push the jogdial to display rEF- and push again.
AIUI appears on the display, by pushing the jogdial again, it will be activated to set the speed by turning.