How can we help you today?

How do I test a Hot Standby PLC that is going to be a standalone system with I/O drop configured if the drop is not present?

Issue
How do I test a Hot Standby PLC that is going to be a standalone system with I/O drop configured if the drop is not present?

Product Line
EcoStruxure Control Expert, Modicon Quantum

Environment
140CPU67160, Control Expert v15.0


Resolution
A standalone Hot Standby PLC with a drop configured but not present will come up in Run Offline mode. In order to boot in Online set %S84 to 1.

Schneider Electric Netherlands

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.