Can I directly connect the voltage inputs of the Sepam 80 on a 415V LV system?
No, the Sepam must not be connected directly to the network.
The continuous thermal withstand of the voltage inputs of the Sepam series 80 is 240 VAC. The Sepam parameter setting tool (SFT2841) does not allow this a voltage to be entered.