How many wires can you install on the Power poles for the LC1D65A contactor?
Issue:
Quantity of wires installed on the Power poles for the LC1D65A contactor.
Product line:
Tesys D, Everlink
Environment:
LC1D40A LC1D50A LC1D65A
Resolution:
The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase. 1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2.
Instruction bulletin attached.
Quantity of wires installed on the Power poles for the LC1D65A contactor.