How can we help you today?

What are the units when reading LCR or motor current over Ethernet on the ATV340 Drive?

Issue:

LCR address 3204 motor current units or values for the ATV340 Drives.

Product Line:

ATV340 Drives.

Environment:

All

Cause:

Motor amps are reading to high over Ethernet or address 3204 LCr.

Resolution:

The unit of LCR are

From ATV340 0.75kw to ATV340 15kw, the unit is 0.01A.

From ATV340 18.5kw to ATV340 75kw, the unit is 0.1A .

Schneider Electric Netherlands

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?